RDCPS2 control and protective switch applies to below load circuits. | ||
Circuit | Utilization Category | Application |
Main Circuit | AC-20 | Making/breaking without load |
AC-40 | Distribution circuit, including mixed resistivity and inductive load | |
AC-41 | AC-42No-inductive or micro inductive load, resistor furnace | |
AC-42 | Slip ring type motor: start, breaking | |
AC-43 | Cage type inductive motor: start, breaking during running | |
AC-44 | Cage type inductive motor: start, reverse connect stop or reverse running, point moving. |
|
AC-45a | Discharge lamp ON/OFF | |
AC-45b | Filament lamp ON/OFF | |
Auxiliary Circuit | AC-15 | Control AC electric magnet |
DC-13 | Control DC electric magnet load |
Main technical datas (main circuits) | ||||||
Frame size | 63 | 125 | ||||
Rated working voltage Ue | 400VAC/690VAC(220VAC custom design) | |||||
Rated isolation voltage Ui | 690V | 800V | ||||
Rated withstand voltage Uimp | 6kV | 8kV | ||||
Conventional thermal current Ith(A) | 12 | 32 | 63 | 80 | 125 | |
Rated working current Ie(A) | 0.6, 1.2, 2.4,6,12 | 18, 32 | 45,63 | 80 | 125 | |
Rated frequency | 50Hz(60Hz custom design) | |||||
Rated operational system (Intermittent duty) | 300 | 120 | ||||
Rated short-circuit breaking capacity Ics | AC400V | 50kA | 50kA | |||
AC690V | 4kA | 6kA | ||||
Utilization Category | AC-43 | |||||
Breaking action time | ≤ 2ms | |||||
Number of poles | 3 |
Main technical datas(Rated working current and control power) | ||||||
Frame size | Conventional thermal current Ie(A) | Rated working current Ie(A) |
Overload current setting range Ir1(A) |
Controllable motor power Pe(kW) | ||
220VAC | 400VAC | 690VAC | ||||
63 | 12 | 0.6 | 0.15-0.6 | 0.04-0.18 | 0.01-0.18 | 0.07-0.3 |
1.2 | 0.3-1.2 | 0.06-0.18 | 0.07-0.5 | 0.13-0.86 | ||
2.4 | 0.6-2.4 | 0.09-0.55 | 0.15-1.0 | 0.25-1.8 | ||
6 | 1.5-6 | 0.25-1.5 | 0.52-2.8 | 0.9-5.0 | ||
12 | 3-12 | 0.75-3 | 1.1-6 | 2.0-10 | ||
32 | 18 | 7.2-18 | 1.5-4 | 3.0-9.5 | 5.0-16 | |
32 | 12-32 | 3-7.5 | 5.0-16.5 | 8.5-29 | ||
63 | 45 | 18-45 | 4-11 | 7.1-23.5 | 14-43 | |
63 | 25-63 | 5.5-18.5 | 10-35 | 19-60 | ||
125 | 80 | 80 | 45-80 | 11-22 | 20-45 | 36-76 |
125 | 125 | 63-125 | 19.5-37 | 28-55 | 51-110 |
Main technical datas(control and auxiliary circuit) | ||||
Frame size rated working current Inm(A) | 63 | 125 | ||
Control Circuit | Control voltage Us(V) | 230VAC 50Hz(60Hz custom design) | ||
Electromagnet coil's Max. power consumption(W) | 4 | 7 | ||
Electromagnet coil's action time(ms) | making: less than 80, breaking: less than 70 | |||
Mechanical life (cycles) | 10 milion | 3 milion | ||
Electrical life(AC-43) ( cycles) | 1 milion | 300,000 | ||
Operation frequency(on-load factor 40%) | 600 | 600 | ||
Auxiliary switch circuit | Number of contacts | 2NO + 2NC | 2NO + 2NC | |
Contact capacity | AC-15 | 230VAC, 5A | ||
DC-13 | ( DC110V,.0.55A), (DC24V, 5A) | |||
Ui:250V,Uimp:4kV,Ith:5A | ||||
Auxiliary status circuit | Number of contacts | 2NO + 1NC | 2NO + 1NC | |
Ue:230VAC ,Ui:250V,Uimp:4kV,Ith:5A | ||||
Controller alarm circuit | Number of output contacts | 1NO | 1NO | |
Ue:230VAC ,Ui:250V,Uimp:4kV,Ith:5A | ||||
Communication circuit module | Ue:24VDC ,Ui:24V,Uimp:0.8kV |