Technical Data
| Item | SP5-10 | SP5-20 | SP5-40 | SP5-60 | SP5-80 | |||||||||||||||
| Nominal discharge current In(8/20us) | 5KA | 10KA | 20KA | 30KA | 40KA | |||||||||||||||
| Max discharge current In(8/20us) | 10KA | 20KA | 40KA | 60KA | 80KA | |||||||||||||||
| Max. continuous operating voltage Uc (V) | 270 | 320 | 385 | 420 | 270 | 320 | 385 | 460 | 270 | 320 | 385 | 460 | 270 | 320 | 385 | 460 | 270 | 320 | 385 | 460 |
| Varistor voltage U1mA (V) | 430 | 510 | 620 | 680 | 430 | 510 | 620 | 710 | 430 | 510 | 620 | 710 | 430 | 510 | 620 | 710 | 430 | 510 | 620 | 710 |
| Protection level Up (kA) | 1.0 | 1.2 | 1.2 | 1.2 | 1.0 | 1.4 | 1.6 | 1.8 | 1.2 | 1.6 | 1.8 | 2.0 | 1.5 | 1.8 | 2.0 | 2.2 | 1.6 | 1.8 | 2.2 | 2.3 |
| Poles | 1P, 2P, 1P+N, 3P, 4P, 3P+N | |||||||||||||||||||
| Rated working voltage Un(V) | 230/400 | |||||||||||||||||||
| Response time (ms) | ≤25 | |||||||||||||||||||
| Test classification | Class II | |||||||||||||||||||
| IP protection class | IP20 | |||||||||||||||||||
| Flame class | V0 | |||||||||||||||||||
| Case material | PBT/PA66 | |||||||||||||||||||
| Recommended fuse or circuit breaker (A) | 40∽60 | |||||||||||||||||||
| Installation method | 35mm DIN rail mounting | |||||||||||||||||||
| Standards | GB/T 18802.11 IEC61643-11 | |||||||||||||||||||
Dimensions